System Mounting Requirements

There are several things that you need to take into account when preparing to

mount the Ultra5000:

• The Ultra5000 must be enclosed in a grounded conductive enclosure

offering protection as defined in standard EN 60529 (IEC 529) to IP55

such that they are not accessible to an operator or unskilled person. A

NEMA 4X enclosure exceeds these requirements providing protection to IP66.

• The ambient temperature of the location in which you will install the

Ultra5000 must not exceed 55° C (131° F).

• You must install the panel on a flat, rigid, vertical surface that won’t be

subjected to shock, vibration, moisture, oil mist, dust, or corrosive vapors.

• You need to maintain minimum clearances (refer to Figure 1.1) for proper

airflow, easy module access, and proper cable bend radius.

Refer to Appendix A for mounting dimensions, power dissipation, and

environmental specifications for the Ultra5000.

IMPORTANT If the cabinet is ventilated, use filtered or conditioned air to

prevent the accumulation of dust and dirt on electronic

components. The air should be free of oil, corrosives, or

electrically conductive contaminates.