Honeywell Digital Input 5K Adapter FC-UDI501

Function

FC-UDI501 is a SIL 3 single channel input module with a 5KOhm shunt resistor for low voltage applications.

Output of the adaptor interfaces with the field device and the input side gets connected to Safety system. 

This module does not require external power to operate.  

Features

• Single channel Digital Input with 5KOhm shunt

• Interface with Universal Safe Input Output Module

Honeywell Universal Pass Through Adapter CC-UPTA01

Function

CC-UPTA01 is a single channel pass through module which allows direct connectivity between Safety System or Safety

field terminals (both live & return) and the field device. This module does not require external power to operate.

Features

• Single channel Pass Through Adapter

• 2 wire AI/AO/DIL/DO/DOL

• System powered field I/O

• HART Pass Through

• Interface with conventional Series C IOMs, Universal IO and Universal Safety IO Module

Honeywell Universal Signal Conditioning Assembly CC-USCA01

Function

CC-USCA01 is a back plane assembly which can accommodate 16 signal conditioning modules. Field side terminals of

each channel is provided with integrated fuse and knife disconnect function. The safety system side interface is provided

through a single System Integration Cable (SIC) which connects all 16 channels. CC-USCA01 is DIN rail mountable.

Features

• Integrated fuse and disconnect function for field side interfaces

• Fuse blown indication for field side fuses

• Disconnect function with current measurement terminals

• 2 wire or 3 wire interface towards field for each channel

• 24V DC power with LED indication

• System Integration Cable (SIC) for 16 channel system side interface

• Screw less assembly to the base plate

• Compatibility with Honeywell IO families: Series C module, Universal IO, Universal Safety IO

Honeywell EP-DOCX-SCA-SMSC-100 Universal IS Signal Conditioning Assembly

• Analog Output Barrier Adapter – FC-UGAO01 is a single channel analog output barrier module, for Intrinsically

Safe Analog Output devices. Output side interfaces with the field device in a non-Safe zone and the input side gets

connected to the USIO module of the safety system. This module does not require external power to operate.

• Digital Input/Output Barrier Adapter – FC-UGDA01 is a single channel digital input or output barrier module, for

Intrinsically Safe Digital Input or Output devices. Output side interfaces with the field device in a non-Safe zone and

the input side gets connected to the USIO module of the safety system. This module does not require external

power to operate.

• Universal IS Signal Conditioning Assembly – CC-UGIA01 is a backplane assembly which can accommodate 16

IS barrier modules. Field side terminals of each channel is provided with integrated fuse and knife disconnect

function. The safety system side interface is provided through a single mass termination cable (SIC) which connects

all 16 channels. CC-UGIA01 is DIN rail mountable.

• Universal Signal Conditioning High Current Assembly – FC-USCA01 is a backplane assembly which can

accommodate 16 signal conditioning modules for high current applications. Field side terminals of each channel is

provided with integrated fuse and knife disconnect function. The safety system side interface is provided through a

single mass termination cable (SIC) which connects all 16 channels. FC-USCA01 is DIN rail mountable.

Universal Signal Conditioning Assembly CC-USCA01

Honeywell EP-DOCX-SCA-SMSC-100 Digital Namur proximity switch Adapter

• Analog Input Adapter, type Sink – FC-UAIS01 is a single channel analog input module which supports source type

sensors. This module does require an external power to operate. This gets connected to the UIO module of the

safety system.

• Digital Namur proximity switch Adapter – FC-UDIN01 is a single channel digital input module for digital proximity

switches. Output side interfaces with the field device and the input side gets connected to the UIO module of the

safety system. This module does not require external power to operate.

• Digital Namur safety proximity switch Adapter – FC-UDNS01 is a single channel digital input module for digital

safety proximity switches.  Output side interfaces with the field device and the input side gets connected to the UIO

module of the safety system. This module does not require external power to operate.

• Analog Input Barrier Adapter – FC-UGAI01 is a single channel analog input barrier module, for Intrinsically Safe

Analog Input devices. Output side interfaces with the field device in a non-Safe zone and the input side gets

connected to the USIO module of the safety system. This module does not require external power to operate.

Honeywell EP-DOCX-SCA-SMSC-100 Digital Output Relay Adapter

• Digital Output Relay Adapter – FC-UDOR01 is a SIL 3 Normally Open single channel relay output module for low

voltage applications. Contact side of the relay interfaces with the field device and the coil side gets connected to

safety system. This module does not require external power to operate.

• Digital Output Relay Adapter F&G – FC-UDOF01 is a SIL 3 Normally Open single channel relay output module for

low voltage applications. The adaptor is capable to drive high current field devices. Contact side of the relay

interfaces with the field device and the coil side gets connected to safety system. This module does not require

external power to operate.

• Analog Input Adapter, type 3 wire – FC-UAIA01 is a single channel analog input module which supports three wire

sensors. Only if used in 3-wire mode, this module requires an external power to operate. This gets connected to the

UIO module of the safety system.

Honeywell EP-DOCX-SCA-SMSC-100 Universal Pass Through Adapter

Functions

• Universal Signal Conditioning Assembly – CC-USCA01 is a backplane assembly which can accommodate 16

signal conditioning modules. Field side terminals of each channel is provided with integrated fuse and knife

disconnect function. The safety system side interface is provided through a single mass termination cable (SIC)

which connects all 16 channels. CC-USCA01 is DIN rail mountable.

• Universal Pass Through Adapter – CC-UPTA01 is a single channel pass through module which allows direct

connectivity between safety system field terminals (both live & return) and the field device. This module does not

require external power to operate.

• Digital Input with 5K resistor Adapter – FC-UDI501 is a single channel digital input module with a 5K resistor for

digital input devices without EOL. Output side interfaces with the field device and the input side gets connected to

safety system. This module does not require external power to operate.

• Digital Input Relay with 5K resistor Adapter – FC-UIR501 is a single channel relay input module with a 5K

resistor for wet contact applications. Coil side of the relay interfaces with the field device and the contact side gets

connected to safety system. This module does not require external power to operate

Honeywell EP-DOCX-SCA-SMSC-100 Universal Marshalling Solution Functions

USCA’s combine multiple functions into a single piece of equipment:

• Plug and Play adapters for optional signal conditioning.

• On-board flexible termination of process signals.

• On-board connection to Safety IOTAs.

• On-board Field power distribution.

• USCA receives 24 VDC power.

• Field disconnect.

• Field fuse.

• Probe points for testing.

• Digital Input with 5K resistor Adapter – FC-UDI501 is a single channel digital input module with a 5K

resistor for digital input devices without EOL. Output side interfaces with the field device and the input

side gets connected to safety system. This module does not require external power to operate.

• Digital Input Relay with 5K resistor Adapter – FC-UIR501 is a single channel relay input module with a 5K

resistor for wet contact applications. Coil side of the relay interfaces with the field device and the contact

side gets connected to safety system. This module does not require external power to operate

• Digital Input Relay Adapter – FC-UDIR01 is a SIL 3 single channel relay input module for low voltage

applications.

Coil side of the relay interfaces with the field device and the contact side gets connected to safety system.

This module does require external power to operate.

Honeywell EP-DOCX-SCA-SMSC-100 Universal Marshalling Solution

Features

Universal Marshaling Solution provides standardized marshalling for central and distributed installations using signal

conditioning assemblies. The signal conditioning assemblies handle 16 I/O’s including disconnect, fusing as default, and

when needed signal conditioning adapters (SCA) including isolation, intrinsic safety, relay, and other functions can be

plugged in optionally. The SCA supports standardized cabinet assembly and wiring configurations without the need for

custom wiring..

The unique features of UMS include:

• Three level flexible field terminations are provided to cater to various field wiring

requirements.

• The Signal Conditioning Adapters are plugged into the USCA to eliminate the

need for a separate installation of isolators, relays, signal converters and barriers.

• USCA has integral (optional) fuse and knife disconnect for easier plant installation

and maintenance.

• D-Sub connector is provided on the USCA for interfacing with the IOTA.

• Field power is supplied through the USCA via the system integration cable (SIC)

from the Safety IOTA.

• Optional power connector is provided to supply power to the active signal

conditioning adapters.

• Optional 16 plug and play Signal Conditioning Adapters.

• Vertical mounting for more effective wiring since most field wiring applications require entry from the top or bottom of

the cabinet.

• An LED for a quick visual cue to draw the Maintenance Technician’s eye to important status information of relay and

active signal conditioning adapters.

Multilin 750/760 Feeder Protection System Digital Relay Protection

Ground Overcurrent Protection

Firmly grounded and low impedance grounded distribution systems require fast ground fault clearance to limit equipment damage.

the 750/760 provides ground fault protection with the following features

– Neutral IOC and TOC

– Grounding IOC and TOC

The 750/760 allows the use of directional elements to supervise ground overcurrent protection elements.

This means that the 750/760 can be used to provide sensitive tripping for unidirectional faults.

Typical applications for directional overcurrent protection include

– Isolating faulty feeders in ring bus or parallel feeder arrangements.

– Protection against faults in the return mains supply from generators in industrial plants

– Sensitive high-speed earth protection for transformers

Sensitive earthing and Restrictive Earth Fault (REF) protection

The sensitive earth and restricted earth fault protection function provides sensitive detection of earth faults.

Sensitive ground fault protection includes

– Instantaneous (50N) and timed (51N) – 2 levels

– Directional monitoring distinguishes between forward and reverse faults.

– Dual polarization (current and voltage) for maximum safety and reliability

750/ 760 for transformer backup protection (grounded converter windings and autotransformers) with RGF function.