8205-TI-IS
• 8 input channels
• Intrinsically safe field circuits
• Thermocouple and mV
• Cold junction compensation
(internal or remote)
• Built-in thermocouple linearisation
• Channels independently configurable
• Open-circuit field wiring detection
MODULE SPECIFICATION
See also System Specification
INPUTS
Number of channels
• 8
THC inputs
• B,E,J,K,N,R,S or T to EN 60584-1: 1995;
• W3 and W5 to ASTM E 988-96
• Russian K and Russian L to rOCT 3044-84
• User definable linearisation table, NOTE 1
Temperature drift
• < ± 0.003% of span/°C
Cold junction compensation error*
• < ± 1°C (– 40 to + 70°C)