Resolution
• 16 bits
Common mode rejection
• >87 dB @ 50/60 Hz
Series mode rejection
• >50 dB @ 50/60 Hz
Common mode voltage between channels
• ± 5 V (max.)
Absolute maximum input voltage
• ± 30 V
Isolation (any channel to Railbus)
• 60 V peak
CONFIGURABLE PARAMETERS
Sensor type
• User selectable
Alarms
• High and low
Input dead zone
• User defined value
Selectable input filtering
• Off / 2 reading avgerage / running avgerage
Drive on open circuit fault
• Disabled / upscale / downscale
Channel status
• Active / Inactive
Cold junction compensation
• Enable / disable / channel number
RESPONSE TIME
Analog signal change to availability on Railbus
• 600 ms (max.)
SAFETY
Field wiring protection
• [EEx ia] IIC
Safety Description (each channel)
• Channels 1. 2. 3. 4. 7 and 8. wired as separate
IS circuits – Uo = 16.4 V, Io = 79 mA, Po = 0.33 W
Channels 5 and 6. wired as separate IS circuits –
Uo = 1 V, Io = 1.1 mA, Po = 0.3 mW
(Input terminals are equivalent to non-energy storing apparatus)
FM entity parameters
• Channels 1. 2. 3. 4. 7 and 8. wired as separate IS
circuits – Voc = 16.4 V, Isc = 63.7 mA, Po = 131mW
• Channels 5 and 6. wired as separate IS circuits –
Uo = 1 V, Io = 1 mA, Po = 0.25 mW