API 670-compliant hot-swappable modules
Remotely selectable limit multiplication and trip bypass
Post-buffered proportional outputs, 0/4-20 mA outputs
Self-test features include monitoring hardware, power inputs, hardware temperature, sensors and cables
Used with displacement www.cniacs.com sensors 6422. 6423. 6424 and 6425 and drivers
con 011/91. 021/91. 041/91
6TE Wide Module for AMS 6000 19″ Rack Mount Chassis
8TE wide module for use with AMS 6500 19″ rack mount enclosure
Sensor Inputs
Number of Inputs Two, independent
Input Type Eddy Current, Differential
Emerson Sensor Input Part Numbers: 6422. 6423. 6424. 6425
Isolation Galvanic isolation
Isolated from power supply
Input resistance >100 kΩ
Input Voltage Range 0 to ±27.3 VDC
Input Frequency Range 0 – 20.000 Hz at 65.535 RPM
Measurement Range
Range Continuously adjustable via configuration software
Minimum range 2 V
Maximum range 0 – 30 V
Sensor power supply Individually buffered sensor power supply galvanically isolated from all system voltages and system supply voltages Open and short circuit protected
Nominal voltage -26.75 VDC
Available current 20 mA nominal, 35 mA maximum
Front Panel Outputs
Green LED: Two LEDs indicating channel OK for each channel
Yellow LEDs: Four LEDs indicating alarms and hazards for each channel.
Separate display for each channel
Front panel buffered outputs:
Two, ±10 V, signal input level reduction factor 0.15. >100 kΩ load, frequency range 0 Hz – 16 kHz (-3 dB)
Mini DIN configuration socket:
Module interface connection for configuration, parameter and status monitoring
RS-232
Handle: for easy removal of the card and to provide module and transducer identification boards