Applications
The 540CID01 is a module in the RTU540 product family consisting of a communication unit (CMU), a multiple input/output module (IOM) and a galvanically isolated wide-range power supply (IOM).
The 540CID01 is a module in the RTU540 product family consisting of a communication unit (CMU), a multi-input/output module (IOM), and a galvanically isolated wide-range power supply (PSM) in a DIN rail metal housing.
Key tasks include
– Managing and controlling the RTU520 I/O module via the serial I/O bus
– Reading process events from the input modules
– Sending commands to the output www.cniacs.com modules.
– Communication with the control system and the local HMI system via serial and Ethernet interfaces.
– Communicates with sub-RTUs, IEDs, or multimeter devices via serial and Ethernet interfaces.
– Manages the time base of the RTU540 product line station and synchronizes the I/O modules.
– Handles the dialog between the RTU540 product line and a web browser via LAN and USB interfaces.
– Acquisition of 8 analog input signals (mA or V signals) with a fast scan cycle of 100 ms for 2 inputs – Acquisition of 16 digital input signals with a fast scan cycle of 100 ms for 2 inputs
Acquisition of 16 digital input signals, 1 high-speed counter input (max. 16 kHz)
– 8 output contacts (normally open), 1-pole or 2-pole outputs
The device is equipped with a battery-buffered real-time clock (RTC).
The device is available in two versions:
– R0001: Process voltage 24 … 60 V DC
– R0002: Process voltage 110 … 125 V DC 125 V DC
Input/Output Controller (IOC)
The microcontroller on the module handles all key tasks for the parameterized processing functions.
In addition, it communicates interactively with the RTU I/O bus. All configuration data and processing parameters are loaded by the communication unit via the RTU I/O bus.
The binary input unit performs the following processing functions for different types of signals:
– Digital filtering to suppress contact jumps
– Suppression of oscillating signals generated during the process
– Intermediate input state with double indication of validity check and suppression
– Consistency check of all channels assigned to digital measured values or step position information
– Summing of incremental pulses to form a combined total in a 31-bit resolution register.
– Copying of the combined total to a freeze register for data storage
The Binary Output Unit can perform the following processing functions for individual signal types:
– Control command output duration
Command monitor function:
– Output relay check on the module (m out of 8)
– Switching voltage monitoring before and during output (24 V DC coil voltage)
– Command output duration monitoring
The analog input unit performs the following processing functions on the measured values:
– Scan period and line frequency interference suppression
– Zero value monitoring and switching detection
– Smoothing
– Threshold monitoring in absolute or cumulative values
– Periodic transmission and background cycling