– 8 single-ended 4-20 mA input channels
– Non-Flammable Field Circuitry
– HART Direct
– HART variable and status reporting
– 2-wire or 4-wire transmitter
– Open and short circuit detection
– Requires 24 VDC bus field power
Inputs
Number of channels
– 8. single-ended
Nominal Signal www.cniacs.com Range (Scale)
– 4 to 20 mA
Full signal range
– 1 to 23 mA
Line Fault Detection
– Short circuit current – > 23.5 mA
– Open circuit current – < 0.5 mA
Output voltage (@ 20 mA)
-13.5 V (min.)
Output current
– 32 mA (max)
Accuracy (over temperature range)
– ± 0.1% of range
Resolution
– 16 bits
Repeatability
– 0.05 of range
Isolation
– Any channel to rail bus – 100 V ac
– Between channels – none
Configurable parameters
Alarms
– High, High-High, Low and Low-Low
Alarm deadband (hysteresis)
– User-defined values