High Level Analog Input System Modules
Three module types are included in the High Level
Analog Input subsystem: a Base Converter module, a
Current Expander module, and a Voltage Expander
module. A typical subsystem will use a Base Convert
er module and (if required) one or more expander modules.
•Base Converter module – catalog number
IC697ALG230
This module has eight differential inputs and
an expansion port. Each input can be individu
ally configured for either voltage or current.
Each of the input channels also has individual
user scaling.
On-board load resistors are included for normal
input current ranges up to Ç 40 mA. If other
current ranges or different resolution is re
quired, external resistors may be used.
Standard system configurations for Ç 10 volts
and 4 to 20 mA are available. These, and other
lower input ranges, can be scaled to engineer
ing units with the user scaling feature.