The following constraints need to be considered when using the
positioner for SIL safety applications:
• Only the 4 to 20 mA setpoint signal is used for the safety
function, all other inputs or not part of the safety function.
• The proof-test specified within this safety manual (or an
equivalent test as specified for the final SIS safety
function) shall be performed before activating the safety
operation and in periodical cycles as demanded by the
final PFDAVG demands.
• The device is installed per manufacturer’s instructions
• The safety-related system (safety logic solver) must be
able to force the 0 mA signal direct or by using a safety
capable switch on the 4 to 20 mA signal.
• Materials are compatible with the final process conditions.
• The environmental, measurement and application limits
stated within the referenced documentations must be
considered accordingly for the SIL safety application.