Whether the link sends in integer or float format must be defined prior to installing the
SM128V. Use the DIP switch to change this setting for each fiber optic link. Each fiber
optic link must be set independently. Data must then be written to the appropriate regis
ters.
The digital channel values may be written in channel-wise in either a DWORD for each
digital channel (bit 0 of each DWORD) or an 8 byte bit mask. Prior to sending the tele
gram the respective registers are OR’d to determine whether a 0 or 1 is sent in the tel
egram. For this reason, it is important to reset the registers of the unused method.
It’s an asynchronous take-over of data from the VME range into the buffer of the FOB
transmitter. Data coming out of the VME range will be synchronized with the 1 ms clock
of the FOB interface. Thus the take-over time for the data varies between 0 and 1 ms.