• Permanently mounts on a single transformer oil
valve. No extra piping or pump required
• “Composite gas” sensor responds 100% to
Hydrogen (general fault gas) and is also sensitive
to Carbon Monoxide (overheated paper)
Acetylene (arcing) and Ethylene (overheated oil)
thus covering main failure root causes
• “Hydrogen only” gas sensor is simpler and
responds 100% to Hydrogen gas only, the
general fault gas
Configurable Alarms
• An alarm is raised when an abnormal level of
fault gas is detected
• Two alarm levels (one for Alert and one for Alarm)
can be set to show increasing severity
• Alarms can be set on gas ppm levels or on gas
rate of change (ROC) over an hour or a day
• Automatic self-test every 15 days will trigger
service alarm if it detects a fault, including power
failure, oil valve closed, sensor or battery needing
replacement