It can be used as restricted earth
fault or, as three functions are included, also as
differential protection on autotransformers, as
differential protection for a tertiary connected
reactor, as T-differential protection for the
transformer feeder in a mesh-corner or ring
arrangement, as tertiary bus protection and so on.
Tripping from Pressure relief/Buchholz and
temperature devices can be done through the
transformer IED where pulsing, lock-out contact
output and so on, is performed. The binary inputs
are heavily stabilized against disturbance to
prevent incorrect operations at for example, dc
system capacitive discharges or DC earth faults.
Distance protection functionality for phase-to
phase and/or phase-to-earth faults is available as
back-up protection for faults within the
transformer and in the connected power system.