The RET670 also features pole slip protection, which detects and evaluates pole slips occurring in the power system and takes the necessary action.
Sections of the power system that are swinging away from each other can be separated by
the line closest to the center of the power swing, allowing the two systems to remain stable when separated.
The RET670 can be used with the IEC 61850-9-2LE process bus with up to six Merge Units (MUs).
Advanced logic functions allow user logic to be programmed with graphical tools to enable special
applications such as automatic opening of disconnect switches in multi-breaker arrangements, closing of breaker loops and load transfer logic.
Logic can be monitored and debugged online in real time for testing and commissioning.
Communication via fiber optic connections ensures immunity to interference.
Six software packages are defined for the following applications:
– Transformer backup protection (A10)
– Voltage control (A25)
– Single-breaker, two-winding transformers (A30)
– Double-winding transformers with multiple circuit-breaker arrangement (B30)
– Three-winding transformers in single-breaker arrangement (A40)
– Triple-winding transformer in multi-breaker arrangement (B40)
The optional functions are not configured, but a maximum configuration with all optional
functions is available as a template in the graphical configuration tool.
Templates for alternative configurations for auto-transformers are also available.
The analog and trip I/O are pre-defined for basic use and come standard with one binary input module and one binary output module.
The binary I/O can be added at the time of ordering, depending on the needs of the application.
the other signals need to be set up according to the needs of the different applications.