Shut-off function
This parameter can be set separately for each end position.
When the respective configured limit value is exceeded, the
shut-off function causes immediate travel of the actuator until
reaching the set end position.
If the value “0” is entered for the corresponding parameter, the
position is further controlled, even in the respective end
position.
Travel time prolongation
This function can be used to increase the max. travel time for
full travel. This time parameter can be set separately for each
direction.
This function can only be used with the pneumatics with the
safety function “fail-safe”.
Switching points for the position
You can use these parameters to define two position limits for
signaling (see option “Module for digital position feedback”).