Using TriStation™ 1131 Workbench software, you

can configure each Triple Modular Redundant (TMR)

UIO point as one of the following:

 Supervised Digital Input, 24 VDC, with 1 ms

Sequence of Events (SOE) capability

 Supervised Digital Output, 24 VDC

 Analog Input, 0-20 mA, configurable: with or

without HART pass-through

 Analog Output, 4-20 mA, configurable: with or

without HART pass-through

The SIE provides:

 Simplified ordering

 Standard cabinet design

 Flexible and scalable I/O deployment without rewiring

 Indoor/outdoor and local/remote installation support

 Support for a maximum of 64 user-configurable points

 Early-stage I/O wiring and late-stage project changes

The SIE has ETPs for termination of field device

signals. Each ETP point comes pre-configured with a

pass-through pluggable conditioning module (PCM).

A range of other PCMs is available.