The IEC 61850 communication implementation supports
monitoring and control functions. Additionally, parameter
settings, disturbance recordings and fault records can be
accessed using the IEC 61850 protocol. Disturbance
recordings are available to any Ethernet-based application in
the standard COMTRADE file format. The relay supports
simultaneous event reporting to five different clients on the
station bus.
The relay can send binary and analog signals to other devices
using the IEC 61850-8-1 GOOSE (Generic Object Oriented
Substation Event) profile. Binary GOOSE messaging can, for
example, be used for protection and interlocking-based
protection schemes. The relay meets the GOOSE performance
requirements for tripping applications in distribution
substations, as defined by the IEC 61850 standard (class P1.
<3 ms data exchange between the devices). The relay also
supports the sending and receiving of analog values using
GOOSE messaging. Analog GOOSE messaging enables easy
transfer of analog measurement values over the station bus,
thus facilitating, for example, the sending of measurement
values between the relays when controlling transformers
running in parallel.