A number of protection functions are available for flexibility in use for different station types and
busbar arrangements. The auto-reclose for single-, two-, and/or three-phase reclose includes priority
circuits for multi-breaker arrangements. It co-oper ates with the synchrocheck function with quick or
delayed reclosing. Several breaker failure functions are included to provide a breaker failure
function independent from the protection IEDs,also for a complete one- and a half breaker diameter.
High set instantaneous phase and earth overcur rent, 4 step directional or un-directional delayed
phase and earth overcurrent, thermal overload and two step under and overvoltage functions are
examples of the available functions allowing user to fulfill any application requirement.
Disturbance recording and fault locator are avail able to allow independent post-fault analysis after
primary disturbances with a single failure in the protection system.
6 x 32 dual directional channels for intertrip and binary signals transfer is available in the commu
nication between selected IEDs inside the station or in a near-by station.
The advanced logic capability, where the user logic is prepared with a graphical tool, allows spe
cial applications such as automatic opening of disconnectors in multi-breaker arrangements, closing
of breaker rings, load transfer logics etc. The graphical configuration tool ensures simple and
fast testing and commissioning.