Design features
Modular construction
– Rectifier, microprocessor control, input/output, power
transformer, filter and alarm assemblies are all modular and
easily replaceable.
Thirty-year life
– All chargers are engineered for greater than 30-year life with
a MTBF of 100.000 hours.
Trouble diagnosis: less than 60 minutes
– Trouble diagnosis and repair in an MTTR of less than 60 minutes.
– All service can be performed from front of opened unit
without disturbing chassis or installed conduit.
Flexible installation
– All chargers can be floor mounted.
– Chargers in style-5018 enclosure can be wall or rack mounted.
Fast, online adjustment
– Control, alarm and operating level set points are adjusted
digitally from the front panel while on line, without the need to
vary loads or external conditions.
Engineered for safety and acceptance
– The battery charger is designed and tested for worldwide applications.
– Meets NEMA 5-1996. PE 5-1997 (R2003) specification
– NEMA-1/IP20 type standard enclosure
– Third party agency approvals:
– CSA C22.2 compliant (up to and including 400A)
– NRTL/C • UL1012/UL1564 compliant
– Seismic qualified (5018/5030 cabinets styles only