Standardized communication
As a standard feature, REF615R supports the IEC 61850
standard for inter-device communication in substations along
with the industry standards DNP 3.0 and Modbus protocols.
The implementation of the IEC 61850 substation communi
cation standard in REF615R encompasses both vertical and
horizontal communication, including GOOSE messaging and
parameter setting according to IEC 61850-8-1. The substation
configuration language enables the use of engineering tools for
automated configuration, commissioning, and maintenance of
substation devices.
The REF615R integrates basic control functionality, which
facilitates the control of one circuit breaker via the relay’s front
panel human machine interface (HMI) or remote control system.
To protect the relay from unauthorized access and to maintain
the integrity of information, the relay has been provided with a
four-level, role-based user authentication system, with individual
passwords for the viewer, operator, engineer, and administra
tor levels