Synchronization of a generator circuit breaker can be
implemented using a single REX640 relay including the
ASGCSYN function block. The relay interfaces the external
measurement and control circuitry via hardwired binary and
analog signals. The excitation and prime mover control signals
are based on pulse commands, either with fixed or variable
length. The synchronizer function block has three different
function modes: manual, semi-automatic and automatic. In
each of these modes, the LHMI acts as the local user interface.
The LHMI includes the necessary command, indication and
measurement features for each of the modes, thus rendering
the conventional dedicated synchronizing panel unnecessary.
REX640 also supports systems in which non-generator circuit
breakers are synchronized. The prerequisite is that all the
feeders within the system are equipped with REX640 relays.
The generator relays have to contain the ASGCSYN function
block and all the non-generator relays need to contain the
ASNSCSYN function block. In addition, all the REX640 relays
have to contain the coordinator function block ASCGAPC.