Arc flash protection
The arc flash protection is available on the optional hardware
module. The module supports connection of up to four sensors.
The sensors can be of lens or loop types, or a free mixture. Both
sensor types are supervised against sensor failure. Fast tripping
increases staff safety and limits material damage, therefore it is
recommended to use static power outputs (SPO) instead of
normal power outputs (PO). This typically decreases the total
operating time with 4..6 ms compared to the normal power
outputs.
The power transformer protection application package also
includes high-impedance differential functions for a phase
segregated protection scheme. If this scheme is applied, the
related current transformers have to be correctly selected and
the necessary secondary circuit components, external to the
relay, defined.