PROVOX I/O Interface Module. The PROVOX I/O Controller
Interface supports redundant Control I/O communications and
connections to Control I/O and Distributed I/O. Distributed I/O
is MUX I/O connected to the controller through the CP6601
serial buffer card.
Controller Carrier. DeltaV controllers mount on a 19 inch rack
specifically designed to accommodate:
• Two DeltaV SQ or SX controllers (one in a simplex installation)
• Two PROVOX I/O Interface modules (one in a simplex installation)
• Two DeltaV system power supplies (one in a simplex installation)
Railbus Connection. The PROVOX I/O Interface Carrier 25 pin
redundant VerticalPLUS railbus connections may be used to
interface with additional DeltaV S-Series I/O modules.
Standard VerticalPLUS DeltaV interface cables are used to
connect the PROVOX I/O Controller Interface Carrier to
traditional DeltaV I/O horizontal carriers. This feature let you
easily expand your system with DeltaV I/O to fully utilize your
DeltaV controller investment.
DeltaV Programmable Serial Cards can connect PLCs and other
serial devices formerly connected to PROVOX IDIs or EICs (non
weigh scale interface option on the EIC).