Several options for closed transition
Once an ATS is in the field, other uses or changes may occur that
could require changes from the original configuration. For example,
an application may initially require that only a closed transition should
be used and if it fails to sync, then the transfer switch will not switch
to the other source and will show an alarm. If the requirements
change and the transfer switch needs to transfer using open transi
tion if closed does not occur, instead of sending the controller back
to the factory for reprogramming, the user can easily change the
transition setpoints to accomplish this.
If the controller is ordered with closed-transition enabled, the
user will have access to options 47C, D, E, F and G, which can be
changed by the setpoints to disable or enable the functions (see
below). Screen 3 of 5 in the system setup menu (See section 3.4.1)
is where the user can set the closed transition options as shown below:
47C = Closed/in-phase/load voltage decay
47D = Closed only (alarm on sync fail)
47E = Closed/in-phase/time delay neutral
47F = Closed/load voltage decay
47G = Closed/time delay neutral