Main disconnecting device

The drive is always equipped with a main disconnecting device.

The device is either the main switch-disconnector inside the module (no option +F253 or +F255),

the main switch-disconnector outside the module (option +F253),

or the main breaker outside the module (option +F255). 

The user operates the main switch-disconnector(s) with a handle on the cabinet door.

The breaker is withdrawable; its must be racked out when disconnection is needed.The supply unit control

program runs in the RDCU control unit located in the swing out frame. 

The RDCU is connected to the supply modules by a fibre optic link, and a separate wire set.

If there are parallel supply modules, the controls from the RDCU are distributed

to the modules with an optical branching unit (APBU board).

The RDCU is also connected to the inverter unit with a fibre optic link and to the panel through the panel

link.

Typically, the user controls the supply unit with the control devices mounted on the cabinet door.

The use of these control devices is described in the following subsections.

No additional control devices or connections are needed.

However, it is also possible to control the unit with the control panel and through the fieldbus.