Control Mode
You can change the control mode by selecting Control Mode from the Mode menu or press
the Hot Key and select Control Mode.
Control Mode lets you define where the instrument receives its set point. Follow the prompts
on the handheld communicator display to choose one of the following control modes: Analog
or Digital.
Choose Analog if the instrument is to receive its set point over the 4 to 20 mA loop. Normally,
the instrument control mode is Analog.
Choose Digital if the instrument is to receive its set point digitally, via the HART
communications link.
A third mode, Test, is also displayed. Normally, the instrument should not be in the Test
mode. The handheld communicator automatically switches to this mode whenever it needs to
stroke the valve, for example during calibration or stroke valve. However, if you abort from a
procedure where the instrument is in the Test mode, it may remain in this mode. To take the
instrument out of the Test mode, select Control Mode then select either Analog or Digital.