Process-level automation: Field devices

Freelance 800F enables you to connect and con

figure PROFIBUS PA devices without directly using a

PROFIBUS PA module for the AC 800F. The LD 800P

Linking Device allows you to operate PA devices on

the PROFIBUS DPV1 module without reducing the

DP bus speed to the lower PA baud rate.Similarly,

the LD 800HSE Linking Device allows you

to connect and configure FOUNDATION Fieldbus H1

devices without the need for an AC 800F fieldbus

module for FOUNDATION Fieldbus H1. The configu

ration of control in the field with FOUNDATION

Fieldbus is supported by Freelance.

HART devices can be connected using HART

compliant modules of the S800/S900.

If the HART devices are connected to the S900.

certain S900 modules can be used to transfer

additional HART values to the cyclical I/O mapping.

This makes it possible to use the second or third

measured values of a HART device in the AC 800F

as an input for applications.