overview display
The process information for the entire plant is pre
sented in a condensed manner in a single overview
display. It offers facilities for selecting the group,
graphic, SFC, Web, time scheduler and trend dis
plays. Logs can also be called up directly from the
overview display. Up to 96 displays (16 lines, each
with 6 displays per line) can be shown in the over
view display. The group display symbols within the
overview display also feature dynamic updating of
process points, allowing disturbance states to be
detected rapidly through appropriate symbols and
colors. If required, you can also set a graphic display
of your choice as overview display. It then replaces
the standardized overview display.
Faceplates
Faceplates allow both overview and detailed informa
tion to be obtained simultaneously. Since faceplates
are predefined, they are available immediately in the
system following the definition of a process point,
without any additional programming.
This is also the case for user-defined faceplates.
Therefore, faceplates can be displayed on a monitor
together with standardized and freely constructed
displays. A selected process point can always be
displayed via its faceplate.