Digital inputs

DM 272/A DM 276/A

Number / wiring of inputs 8x sink 6x source

Input type Type 1 (acc. to EN 61131-2)

Voltage range for “1” 15 V ≤ UH ≤ 30 V

Voltage range for “0”-3 V ≤ UL ≤ 5 V

Debouncing Configurable 1 ms, 100 ms

Cycle time 1 ms

Status display Green LED

Galvanic isolation Yes, electric strength 707 V with isolated ground connection

Interrupt inputs

Number of inputs Two of the digital inputs can be used as interrupt inputs

Voltage range for “1” 15 V ≤ UH ≤ 30 V

Voltage range for “0”-3 V ≤ UL ≤ 5 V

Response time of the K-bus interrupt 50 μs

Status display Green LED

Galvanic isolation Yes

Digital outputs

DM 272/A DM 276/A

Number / wiring of outputs 8x source 8x sink

Nominal voltage 24 V DC

Processing time 1 ms

Nominal current of digital outputs 2 A at 50 % simultaneity

Protection facility Short-circuit protection

Max. inductive load 1 J at max 0.2 Hz

Status display Orange LED

Galvanic isolation Yes, from the control electronics and between one another,

electric strength 707 V with isolated ground connection

Dimensions, weight

Height 120 mm

Width 22.5 mm front plate / 32.5 mm incl. K-bus plug

Depth 100 mm

Weight 135 g

Environmental conditions

Operating temperature +5 °C … +55 °C

Storage temperature-40 °C … +70 °C

Relative air humidity 10 % to 95 % (non-condensing)

Vibration resistance / shock resistance Acc. to EN 61131-2

General

Supply voltage 24 V DC from front

(nominal voltage tolerance: 19.2 V to 30 V, acc. to EN 61131-2)

24 V DC from K-bus, 5 V DC from K-bus

Overvoltage category II

Protection class III acc. to EN 61131-2

Addressing on K-bus Via 16-digit address switch, on the side

Type of terminals Open – pitch 5.08 mm

Max. power consumption K-bus 24 V 1.9 W