Analog inputs
AM 280/A AM 282/A AM 280/B
Number of inputs 4 4 4
Type Voltage input Voltage input Current input
Resolution 14 bit 16 bit 14 bit
Signal range ±10 V or 0 – Uref (10 V) ±10 V or 0 – Uref (10 V) 0 – 20 mA or 4 – 20 mA
Max. measurement signal ±10.4 V ±10.4 V-0.8 mA … 20.8 mA
Input type Differential or single-ended Differential or single-ended Differential
Galvanic isolation No No No
Reference voltage output 10 V ±2.5 %; max. 20 mA 10 V ±2.5 %; max. 20 mA
Scan repeat cycle 1 ms 1 ms 1 ms
Input impedance in signal range 10 MΩ 10 MΩ < 200 Ω
Input filter characteristic First order First order First order
Limiting frequency of the input filter 250 Hz 250 Hz 250 Hz
Conversion method Successive approximation Successive approximation Successive approximation
Monotonicity without error codes Yes Yes Yes
Common mode range ±13.5 V ±13.5 V ±13.5 V
Common mode rejection ratio > 80 dB > 80 dB > 80 dB
Value of the lowest bit (LSB) 1.3 mV 1.3 mV 1.35 μA
Maximum permitted continuous load
(without damage) ±30 V
Typ. temp. coefficient measurement error ±5 ppm of scale end value / °C
Max. temp. coefficient measurement error ±20 ppm of scale end value / °C
Largest error at 25 °C ±0.01 % of scale end value