Advice
Single or dual-channel?
Not every synchronizing system needs to be structured
according to the above pattern. The SYNCHROTACT® 5
single-channel synchronizing devices offer a high degree of
security and are often used in practice. However, security
can be significantly increased by means of dual-channel
systems. It is unlikely that the two channels – of which the
hardware and software are structured differently – will have
the same malfunction simultaneously. The extra cost of a
dual channel system can prove beneficial compared to the
damage arising from incorrect paralleling.
Second, redundant synchronizing system?
Often, two redundant synchronizing systems are installed
in a single plant so that, in the event of one system failing,
the other can be used, thereby increasing availability. The
second system is often designed for manual synchronizing
with or without synchrocheck.
In addition, with SYNCHROTACT® 5. ABB offers two automatic
dual-channel systems in a single casing, thus avoiding
manual synchronizing.