SYNCHROTACT® Accessories

Auxiliary device SYN 5500

The auxiliary device SYN 5500 connects the measuring

and command circuits where several paralleling points

need to be switched. An SYN 5500 device can switch two

paralleling points, each with a maximum of 16 contact pairs,

or alternatively, four paralleling points, each with eight contact

pairs. Several devices can be used at the same time.

Technical data

Maximum contact voltage   250 VAC/VDC

Limiting continuous current  10 A

Maximum switching power ON AC/DC  1500 VA/W

Maximum switching power OFF AC/DC (resistive) 1500/150 VA/W

Coil nominal voltage 24 VDC

Operate voltage  > 18 VDC

Release voltage < 3.6 VDC

Coil resistance 1152 Ω

Coil inductivity 1000 mH

Casing size (W x H x D)  381 x 128 x 50 mm

Hat rail mounting (DIN)

Electromechanical instruments are commonly used if the

synchronizing system provides a manual synchronizing

feature. Sometimes the instruments are used in automatic

synchronizing systems for information only, eg, for servicing

purposes. This requirement can also be covered by the

SYNCHROTACT® 5 PC-tool SynView.