When are adaptation or compensation VTs needed?
– If the two nominal measuring voltages are out of admissible
range (50 to 130 VAC).
– If the two nominal measuring voltages are different. With
the types SYN 5200 and SYN 5201. differences between
the nominal values up to 10 % can be tuned by parameter
setting. – If there is a step-up transformer between measuring VT and
circuit breaker, which shifts the phase by a fixed value, it
can be compensated with types SYN 5200 and SYN 5201.
With the types SYN 5100. SYN 5202. SYN 5302. or with
the use of electromechanical synchronizing instruments,
compensation VTs shall be used in order to compensate for
the phase shift.
If a three-phase compensation is inevitable, 3 single-phase VTs
have to be selected which will then be connected according
to the needs. Be aware that the single phase ratio has to
be calculated.