Wide operating temperature range
The sturdy electronics design of the AMC 600 gives it a design lifetime of 10 years
at 40 °C ambient temperature, and the ability to operate from -40 to 70 °C. As a result,
you can use the AMC 600 all over the world. It can start from -40 °C and
can be stored from -40 to 85 °C. It will operate at a relative humidity
from 5 to 97% (condensing at 55 °C). This contributes to lower service costs,
and the long lifetime ensures high value for your investment and minimises electronic waste.
Robust and well protected
The AMC 600 is designed for robustness based on the proven AWC 500 design.
The base-mounted rack design makes the AMC 600 resistant to bumps (25 g),
shocks (50 g), and vibrations, even during transportation.
The backplane interconnection of the I/O modules ensures reliable communication
in harsh environments, avoiding long-term damage often seen with slide-in contacts.
The flanges ensure improved grounding to increase protection against EMC,
and its built-in protection circuits safeguard the controller from surges and
fast transients up to 4kV, electrostatic discharge up to 6kV.
Leave a comment