The F30 is compatible with F304. F308 and F312 Megablock
types, typically providing up to 12 Ex ic spurs per fieldbus
segment. Up to two F30s and their associated Megablocks
may be connected to a single segment, to allow the fieldbus
trunk to be extended between junction boxes in the field.
The spurs are compatible with FISCO and Entity certified
fieldbus instruments. Where FISCO instruments are selected,
cable parameter calculations are not required.
To comply with intrinsic safety requirements, each fieldbus
segment must be powered by a 918x-x2 fieldbus power
supply, fitted with 9192-FP power modules.
Ex ic replaces the earlier Ex nL technique for energy-limited
fieldbus networks, and brings the technique into line with
formal intrinsic safety procedures.
A key benefit of the MTL Ex ic spur solution is that the
fieldbus power supply has a higher output voltage than
competing products, allowing longer trunk cable lengths and
more fieldbus instruments per segment. Requirements for
ensuring compatibility with major host control systems are
also simplified.
The F30 is designed for installation in the field enclosure
together with the Megablock wiring hub. A full range of
compatible stainless steel and glass reinforced polyester
(GRP) enclosures are available.
Leave a comment