The F809F-Plus is available with fully updated versions of eEDDL and FDT/DTM user interfaces

that are free to download from the eaton.com website. Improvements include faster operation

and clearer screen layouts, leading to an enhanced user experience. The user interfaces comply

with NAMUR specification NE107 ‘Self-Monitoring and

Diagnosis of Field Devices’, providing clear standardised diagnostic alerts using three of the four

categories; maintenance required, out of specification, and failure.

Certifications and compliances

EU ATEX:

• Ex II 3 G Ex nA IIC T4 (-40oC=Ta=+70oC)

EU ATEX:

• Ex nA IIC T4 Gc (-40oC=Ta=+70oC)

North America (FM/cFM):

• US: NI/1/2/ABCD T4 (-40oC=Ta=+70oC);  1/2/AEx nA/IIC/T4 (-40oC=Ta=+70oC)

• Canada: NI/I/2/ABCD/T4 (-40oC=Ta=+70oC);  I/2/ExnA/IIC/T4 (-40oC=Ta=+70oC)

Environmental ratings:

• IP rating: IP20 to BS EN 60529 (Additional protection by means of enclosure)

• Operating Temperature: –40°C to +70°C*

• Corrosive atmospheres: Designed to meet ten year service in Class G3 corrosive environment, as defined by ISA Standard SP71.04

* When mounted in a vertical orientation (optimum orientation)

Design features

• Monitors health of 8 fieldbus segments

• Provides early indication of possible network failure

• Communicates over Foundation™ fieldbus H1 segment

• Easily integrates into any fieldbus control system

• Registered to Fieldbus Foundation ITK 6.0. including support for Resource Block diagnostic bits

• Network status and parameters displayed in instrument management software

• Updated EDDL and FDT/DTM user interfaces, with Namur NE107 compatible alarm categories