Device
The address (in decimal and hexadecimal) and signal level of each
device on the network is displayed in turn by pushing the “SELECT”
button. On Foundation fieldbus™ networks, the first device shown
will be the LAS. Measurements greater than 150mV are OK.
Average Noise
Displays the average noise based on the average of the last 100
noise measurements. Noise levels are measured and displayed in 3
frequency bands: frequencies in the fieldbus signalling band (Fieldbus
Frequency, FF), frequencies below the fieldbus signalling band (Low
Frequency, LF) and frequencies above the fieldbus signalling band
(High Frequency, HF). The particular frequency band displayed is
selected by pushing the “SELECT” button. Measurements of less
than 75mV are OK.
Peak Noise
Displays the peak noise recorded since the Monitor was connected.
The value displayed is the highest noise level measured since the last
reset. Peak noise levels are measured and displayed in the same three
frequency bands as average noise. Measurements of less than 75mV
are OK.