Do not mount the C7400S, C7250A “Grey Sensors”
directly against mounting surface.
We’ve found that sensors do not read the proper
temperature and humidity readings if they are mounted
directly on a surface. This is due to the radiant and
convective temperature coupling of the metal surfaces to
the sensor case, which causes the sensor to accurately
measure an average of the surface and the air. Use the
50053060-001 sensor mounting bracket if you apply
these sensors.
Address grey sensors via addressing settings before
installation.
Refer to this document and other technical information to
set these switches correctly before installation. If these
switches are not set correctly, the sensor will fail to
function properly.
Set jumpers and scale sensors.
It is essential to set physical jumper Honeywell current
sensors. You need to match this scaling, either via LCBS
Connect wall module or LCBS Connect Web UI. If you
don’t, CT output will read incorrectly.