Set jumpers and scale sensors.
It is essential to set physical jumper Honeywell current
sensors. You need to match this scaling, either via LCBS
Connect wall module or LCBS Connect Web UI. If you
don’t, CT output will read incorrectly.
Set differential pressure sensors, set switches.
Make sure that you set the physical switches on the
Honeywell P7640 device to measure 0 to 2.5 inches of
water column. Please check this setting on the sensor.
Further, you will need polyethylene tubing running to the
high pressure side of the filter. Please refer to installation
information if you need help determining proper poly tube
positioning relating to the filter.