Overvoltage unit
When the voltage values exceed the set start value of low-set stage U>, the overvoltage
unit will start to deliver a start signal after a ~60 ms’ start time. When the set operate time
at definite-time characteristic or the calculated operate time at inverse definite mini
mum time (IDMT) characteristic elapses, the overvoltage unit will deliver a trip signal.
When the voltage values exceed the set start value of high-set stage U>>, the overvoltage
unit will start to deliver a start signal after a ~50 ms’ start time. When the set operate time
at definite-time characteristic or the calculated operate time at IDMT characteristic
elapses, the overvoltage unit will deliver a trip signal.
The low-set and the high-set stage of the overvoltage unit can be given either a defi
nite-time or an IDMT characteristic. At IDMT characteristic, two time/voltage curve
groups, A and B, are available.
It is possible to block the tripping of an over voltage stage by applying an external binary
input signal to the relay.
The high-set stage can be set out of operation. This state will be indicated by dashes on the
LCD and by “999” when the set start value is read via serial communication.