Product Description and Specification 

DeltaV Flex.Connect solutions provide direct connection from 

Foxboro I/A Series 100 I/O to DeltaV Electronic Marshalling. 

The following Foxboro I/A Series 100 I/O FBM point types have 

DeltaV Flex.Connect solutions as described below: 

Series 100 

DeltaV Flex.Connect solutions passive nosecone adapters and 

cables connect FBM terminal blocks to standard DeltaV AI, AO, 

DI, and DO CHARM terminal blocks via a passive DIN-rail mount 

nosecone adapter (see Figure 1). 

◼ Analog Inputs FBM01 

8 Analog Inputs connect to 8 4-20mA AI HART CHARMs 

◼ Analog Inputs/Outputs FBM04 

4 Analog Inputs and 4 Analog Outputs connect to 4, 4-20mA 

DeltaV AI HART & 4, 4-20mA DeltaV AO HART CHARMs

◼ Digital Inputs FBM07A/12A 

16 Digital Inputs connect to 16, 24 VDC DeltaV DI 24 VDC Isolated 

CHARMs 

◼ Digital Inputs FBM07B/12B 

16 Digital Inputs connect to 16 24VDC Low-Side Sense (dry 

contact) CHARMs 

◼ Digital Inputs FBM08/13 

16 Digital Inputs connect to 16 120 VAC Isolated CHARMs 

◼ Digital Inputs/Outputs FBM09A 

8 Digital Inputs (external power source) connect to 8 24VDC 

Isolated CHARMs and 8 Digital Outputs connect to 8 24VDC 

Isolated CHARMs 

◼ Digital Inputs/Outputs FBM09B 

8 Digital Inputs (internal power source) connect to 8 24VDC 

Isolated CHARMs and 8 Digital Outputs connect to 8 24VDC 

Isolated CHARMs 

◼ Digital Inputs FBM09C 

8 Digital Inputs (external power source) connect to 8 24VDC 

Low-Side Sense (dry contact) CHARMs and 8 Digital Outputs 

connect to 8, 24VDC Isolated CHARMs 

◼ Digital Inputs FBM09D 

8 Digital Inputs (internal power source) connect to 8 24VDC 

Isolated CHARMs and 8 Digital Outputs connect to 8 24VDC 

Isolated CHARMs 

◼ Digital Inputs FBM10/15 

8 Digital Inputs connect to 8 120VAC Isolated CHARMs and 8 

Digital Outputs connect to 8 120VAC High Side CHARMs