Product Description and Specification
DeltaV Flex.Connect solutions provide direct connection from
Foxboro I/A Series 100 I/O to DeltaV Electronic Marshalling.
The following Foxboro I/A Series 100 I/O FBM point types have
DeltaV Flex.Connect solutions as described below:
Series 100
DeltaV Flex.Connect solutions passive nosecone adapters and
cables connect FBM terminal blocks to standard DeltaV AI, AO,
DI, and DO CHARM terminal blocks via a passive DIN-rail mount
nosecone adapter (see Figure 1).
◼ Analog Inputs FBM01
8 Analog Inputs connect to 8 4-20mA AI HART CHARMs
◼ Analog Inputs/Outputs FBM04
4 Analog Inputs and 4 Analog Outputs connect to 4, 4-20mA
DeltaV AI HART & 4, 4-20mA DeltaV AO HART CHARMs
◼ Digital Inputs FBM07A/12A
16 Digital Inputs connect to 16, 24 VDC DeltaV DI 24 VDC Isolated
CHARMs
◼ Digital Inputs FBM07B/12B
16 Digital Inputs connect to 16 24VDC Low-Side Sense (dry
contact) CHARMs
◼ Digital Inputs FBM08/13
16 Digital Inputs connect to 16 120 VAC Isolated CHARMs
◼ Digital Inputs/Outputs FBM09A
8 Digital Inputs (external power source) connect to 8 24VDC
Isolated CHARMs and 8 Digital Outputs connect to 8 24VDC
Isolated CHARMs
◼ Digital Inputs/Outputs FBM09B
8 Digital Inputs (internal power source) connect to 8 24VDC
Isolated CHARMs and 8 Digital Outputs connect to 8 24VDC
Isolated CHARMs
◼ Digital Inputs FBM09C
8 Digital Inputs (external power source) connect to 8 24VDC
Low-Side Sense (dry contact) CHARMs and 8 Digital Outputs
connect to 8, 24VDC Isolated CHARMs
◼ Digital Inputs FBM09D
8 Digital Inputs (internal power source) connect to 8 24VDC
Isolated CHARMs and 8 Digital Outputs connect to 8 24VDC
Isolated CHARMs
◼ Digital Inputs FBM10/15
8 Digital Inputs connect to 8 120VAC Isolated CHARMs and 8
Digital Outputs connect to 8 120VAC High Side CHARMs