Specifications
Limit Controller
• Microprocessor-based limit controller
• Nominal switching hysteresis, typically 3°F (1.7°C)
• High or low limit, factory selectable
• Latching output requires manual reset upon over or
under temperature condition
• Manual or automatic reset on power loss, factory
selectable
• Internal front panel or external customer supplied
momentary reset switch
• Input filter time: 1 second
Operator Interface
• 4 digit, 7 segment LED displays, 0.28 in. (7 mm) high
• °F or °C indicator LED
• Alarm indicator LED
• Continuous turn, velocity sensitive rotary encoder for
set point adjustment
• Front panel SET/RESET
Standard Conditions for Specifications
• Rated line voltage, 50 to 60Hz, 0 to 90% RH
non-condensing, 15-minute warm-up
• Calibration ambient range: 77°F (25°C) ±3°C
Sensor Input
Thermocouple
• Grounded or ungrounded
• Type E, J, K, T thermocouple
• >10 MΩ input impedance
• 250 nV input referenced error per 1Ω source
resistance
RTD
• 2-wire platinum, 100Ω
• DIN-curve (0.00385 curve)
• 125μA nominal RTD excitation current
Input Accuracy Span Range
Type E: -328 to 1470°F (-200 to 800°C)
Type J: 32 to 1382°F (0 to 750°C)
Type K: -328 to 2282°F (-200 to 1250°C)
Type T: -328 to 662°F (-200 to 350°C)
RTD (DIN) -328 to 1472°F (-200 to 800°C)
Thermocouple Input
• Calibration accuracy: ±1% of input accuracy span,
±1° at standard conditions and actual calibration
ambient. Exception: Type T, ±2.4% of input accuracy
span for -328 to 32°F (-200 to 0°C)
• Temperature stability: ±0.3° per degree change in
ambient
RTD Input
• Calibration accuracy ±1% of input accuracy span ±1°
at standard conditions and actual calibration ambient
• Temperature stability: ±0.2° per degree change in
ambient