Specifications

Limit Controller

• Microprocessor-based limit controller

• Nominal switching hysteresis, typically 3°F (1.7°C)

• High or low limit, factory selectable

• Latching output requires manual reset upon over or

under temperature condition

• Manual or automatic reset on power loss, factory

selectable

• Internal front panel or external customer supplied

momentary reset switch

• Input filter time: 1 second

Operator Interface

• 4 digit, 7 segment LED displays, 0.28 in. (7 mm) high

• °F or °C indicator LED

• Alarm indicator LED

• Continuous turn, velocity sensitive rotary encoder for

set point adjustment

• Front panel SET/RESET

Standard Conditions for Specifications

• Rated line voltage, 50 to 60Hz, 0 to 90% RH

non-condensing, 15-minute warm-up

• Calibration ambient range: 77°F (25°C) ±3°C

Sensor Input

Thermocouple

• Grounded or ungrounded

• Type E, J, K, T thermocouple

• >10 MΩ input impedance

• 250 nV input referenced error per 1Ω source

resistance

RTD

• 2-wire platinum, 100Ω

• DIN-curve (0.00385 curve)

• 125μA nominal RTD excitation current

Input Accuracy Span Range

Type E: -328 to 1470°F (-200 to 800°C)

Type J: 32 to 1382°F (0 to 750°C)

Type K: -328 to 2282°F (-200 to 1250°C)

Type T: -328 to 662°F (-200 to 350°C)

RTD (DIN) -328 to 1472°F (-200 to 800°C)

Thermocouple Input

• Calibration accuracy: ±1% of input accuracy span,

±1° at standard conditions and actual calibration

ambient. Exception: Type T, ±2.4% of input accuracy

span for -328 to 32°F (-200 to 0°C)

• Temperature stability: ±0.3° per degree change in

ambient

RTD Input

• Calibration accuracy ±1% of input accuracy span ±1°

at standard conditions and actual calibration ambient

• Temperature stability: ±0.2° per degree change in

ambient