The fieldbus barrier is mounted in a 316L stainless steel,
increased safety, Ex e enclosure that segregates spur and
trunk cabling in accordance with hazardous area certification.
Inside the enclosure, the incoming trunk wiring terminates
in a separate compartment containing increased safety (Ex
e) trunk wiring terminals. This compartment has a protective
cover to deter interference, and carries a warning to the user
not to work on trunk wiring without first isolating the power.
A fieldbus terminator is included for the trunk wiring to ensure
correct termination of the wiring and prevent unwanted
reflections and signal disturbances.
The system described in this manual provides 12 spurs of
“simplex” type – meaning they are not intended to provide
redundancy between spurs. Each spur is short circuit
protected, so that other devices continue to operate in the
presence of field wiring faults.