The F30 adaptor
The F30 adaptor is connected in series with the trunk wiring to the Megablock (see
Figure 2.1) and limits the voltage to ensure that the ‘Uo’ at the Megablock spurs is
less than the 17.5V value required for compatibility with FISCO-certified instruments.
Where the voltage arriving at the F30 is higher than this (for example, if the trunk
cable is only short in length resulting in only a small voltage drop in the cable), the
F30 regulates the voltage to less than 17.5V. Final current limiting for each spur is
provided by the short-circuit limiting circuits built in to the F300 Megablock, for which
Ex ic approval already exists. As a result, the combination of F30 and F300 meets the
requirements for Ex ic voltage and current limitation.
The F30 is designed for use only with MTL F304. F308 and F312 Megablock types,
typically providing up to twelve Ex ic spurs per fieldbus segment. These spurs
may be all from one F312 Megablock in one enclosure, or distributed between two
separate enclosures – see Section 4.7.
The spurs are compatible with FISCO and Entity certified fieldbus instruments, and
where FISCO instruments are selected, cable parameter calculations are not required.