Overload Curves
The curves can take one of three formats: standard, custom, or voltage dependent.
For all curve styles, the 469 retains thermal memory in a thermal capacity
used register which is updated every 0.1 second. The overload pickup determines
where the running overload curve begins.
The 469 standard overload curves are of standard shape with a multiplier value of
1 to 15.
The voltage dependent overload curves are used in high inertia load applications,
where motor acceleration time can actually exceed the safe stall time and motor
thermal limits. During motor acceleration, the programmed thermal overload curve
is dynamically adjusted with reference to the system voltage level. The selection
of the overload curve type and the shape is based on motor thermal limit curves
provided by motor vendor.