High Burden Application
These relays, supplied as high burden, are suitable for use in high
security circuit-breaker tripping circuits. The high burden provides
greater immunity to capacitance discharge currents, which can
result at the inception of an earth fault on battery wiring. This
makes the relays particularly suitable for use in distributed
tripping or control relay contact logic schemes, where the
initiating contact may be remote from the relay.
MVAJ 05
When configured for high burden applications, the burden is
either cut off at operation or is economised to a low figure
instantaneously.
Low Burden Application
These relays are suitable for general applications where the
initiating contact is located close to the relay. When configured
for low burden applications, by removing the external link from
terminals 22 and 24. the burden is either cut off during operation
or is economised to a low figure instantaneously.