The MVAJ 11 to 34 range complements the more cost-effective range of MVAJ 051 to
MVAJ 205 tripping relays catering for the preferences of historical users.
MVAJ general characteristics can be found in table 1 that includes information on how
relay burden is modified at, or just after operation. ‘Economy’ indicates that the burden
reduced to a low value.
Instantaneous cut-off is a feature of some hand and electrical-reset elements and
the burden to zero, whilst others incorporate a time delay to enable series elements
operate. This time delay is 40 ms to 60 ms in all cases, except that of type MVAJ 26
the delay is 2 s. All low burden relays are suitable for AC or DC operation. All high
relays are for DC operation only.
Types MVAJ 23. 25 High Burden Tripping Relays
with Instantaneous Cut-off
These relays incorporate a break contact in series with the
operate coil. Located on the main contact stack, it is arranged to
break the coil circuit once the relay mechanism has completely
operated. This reduces the relay burden to zero as soon as
mechanical latching of the contacts has occurred.