Flex I/O Scanner
This operating mode allows PLC’s on Remote I/O to connect to and control 1794-AENT
EtherNet/IP Flex adapters.
• Designed to replace obsolete 1794-ASB adapters
• Supports up to 16 EtherNet/IP connections
• Each adapter and rack of discrete counts as a single connection. Each analog module
counts as a single connection.
Remote I/O Scanner
This operating mode allows users to replace their existing Remote I/O PLC with a ControlLogix
or CompactLogix PAC without having to replace existing racks of I/O.
• Build new controller programs without interrupting existing controls, minimizing downtime
• Supports up to 32 racks of Remote I/O
• Supports all Remote I/O baud rates (57.6. 115.2. and 230.4 K baud), and Remote I/O
addressing 0 to 76 octal
• Auto-Configuration utility discovers baud rate and maps discrete I/O, reducing configuration
errors