Configuration
ProSoft 61850 Configuration Manager software, provided with the gateway, is used to develop and manage gateway
configuration files, as well as to view communication and network diagnostics.
Import CID and SCD files
Drag and drop IEC 61850 Data Attributes for Modbus mapping
PLC or PAC Tag names are automatically created
Print mapped tag list
Tag file export (.CSV)
Export .XSY (Variable) and .XFM (Function Block) files for use with Unity Pro
Specifications – Modbus TCP/IP
The Modbus TCP/IP driver allows multiple independent, concurrent Ethernet
connections. The connections may be Clients, servers, or a combination of both Clients
and servers.
Modbus TCP/IP Client
Actively reads data from and writes data to Modbus TCP/IP devices using MBAP
messages on Service Port 502 or Encapsulated Modbus RTU messages on other
Service Ports.
Supports up to 10 Client connections (max. 2000 commands) to multiple servers.
Modbus Command optimization – Multiple tags can be combined into one Write
command with up to 120 words.