Application/Description

From the Fire Brigade Panel BU-210 it is possible to mute

the panel’s internal buzzer, silence sounders/bells etc.

and reset the system. Only alarms are shown in the

display.

The panel is menu operated on a 8-line display, with 40

characters per line.

The BU-210 communicates with the Fire Alarm Control

Panel BS-200. Information Panels BV-210. Repeater

Panels BS-211. other Fire Brigade Panels BU-210 and

Mimic Drivers BUR-200 on an RS-485 panel bus.

Indicators

  8 x 40 character alphanumeric display

 Alarm, More Alarms, Pre-Alarm, Remote Call, Fault,

Disabled Function, Delayed Activation, Power

 Internal buzzer

Operator Controls

 More Events, Mute panel, Silence, Reset

 Backlit buttons and text

 Fireman’s key

Capacity

 A maximum of 8 additional panels can be freely

mixed and connected to the Fire Alarm Control Panel

via the RS-485 panel bus, including Repeater Panels

BS-211. Information Panels BV-210. Fire Brigade

Panels BU-210 and mimic Drivers BUR-200