Cyclic Load Motor Applications
Input currents of a motor driving cyclic load can vary between very low
to above the maximum allowable current during a load cycle. Variation in
current magnitude results in motor heating and cooling depending on the
heat and cooling time constants. Thermal overload protection response
is made adaptive to the cyclic load based on the cooling time constants.
In addition, to provide more accurate overload thermal model response
to cyclic load, the input currents to the thermal model are averaged over
the settable duty cycle interval. With a reciprocating load application, the
number of cycles to average can be determined from current waveform
capture using the Oscillography/Datalogger features in the 869 motor
protection relay.